Digital Output Field Interface Module 2C/O Contacts with Wetted Contacts with Fuse
Applications :
Digital Output Relay Interface Module 1C/o with Wetted Contacts & Fuse used as Interface between PLC/ DCS/Drives digital outputs to field or field devices such as Contactor, Solenoid Valve, Motors and etc Outputs are galvanically isolated through relays
TECHNICAL DATA
Input Data (FIELD SIDE):
| Operating Voltage | 24VDC |
| Input Current/Chnl | 25mA @ 24VDC |
| Input Wiring | Source type OR specify |
| Protection (Coil) | Free wheeling diode |
| Indication/Chnl | LED |
| Termination (System) | D Type or FRC |
Output Data (SYSTEM SIDE)
| Contact Type | DPDT (2C/O) |
| Max Output Current | 5A @230VAC/30VDC |
| Output Wiring | Wetted (Powered Contacts) |
| Protection | Fuse & Fuse Fail Indication |
| Max. Voltage | 250VAC/DC |
| Termination Field | Screw type Terminal Blocks |
Component Specification:
| Relay | 24VDC Coil, 2 C/o |
| Socket | 2C/o PCB Solderable Type |
| Terminals | Screw Type (2.5Sq mm) |
| PCB | Glass Epoxy Double Sided |
General Data
| No. of Channels | 8, 16 |
| Test Voltage | 2.5kV, 50Hz, 1M |
| Mounting | Universal Dinrail Mountable |
| Identification Tag | Optional (On request) |
Standards & Approval
| *PCB: Type tested STQC, IEC |
| 61373, *ANSI IPC 319 MIL 275B |
| *Terminals: UL/CE & CSA |
| *Ambient Opt Temp: | Max 60 Deg.C |
| *Relative Humidity: | Max 60 Deg.C |
| TYPE OF CARD |
Length |
Width |
| BRM8-24DDO-2B-WFi-D15 | 160 | X | 126 |
| BRM16-24DDO-2-WFi-D25 | 305 | X | 126 |
| BRM8-24DDO-2B-OFi-D15 | 150 | X | 126 |
| BRM16-24DDO-2B-OFi-D25 | 290 | X | 126 |